Fire Extinguisher Inspection

Portable fire extinguishers must be inspected at least monthly. Check the following items regarding portable fire extinguishers when evaluating the FPP:

Extinguisher Inspection
  • A minimum of one 2A-10:BC portable fire extinguisher should be provided within 75 feet of travel distance from anywhere in the business on each floor.
  • Fire extinguishers should be inspected at least monthly.
  • Fire extinguishers should not be obstructed and should be in a conspicuous location.
  • When visually obstructed, an approved means should be provided to indicate location of fire extinguishers.
  • Fire extinguisher should be mounted on the wall with a hanger.

Monthly Inspection Requirements

  • Inspect to ensure proper condition and function.
  • Record the inspection date and the inspector's initials on the inspection tag.

Steps to Inspect a Fire Extinguisher

  • Confirm accessibility: Make sure the extinguisher is not blocked and can be easily reached.
  • Check mounting: Ensure the extinguisher is mounted securely on a wall hanger or bracket.
  • Verify pressure: The needle on the pressure gauge should be in the green (operable) zone.
  • Inspect condition: Look for dents, corrosion, leaks, or other physical damage.
  • Confirm label and instructions: Instructions should be legible and face outward.
  • Check pin and seal: The pull pin should be in place and the tamper seal unbroken.

Placement and Visibility Requirements

  • At least one 2A-10:BC extinguisher must be located within 75 feet of travel distance from any point on each floor.
  • Extinguishers must be placed in a conspicuous, accessible location.
  • If visibility is blocked, use an approved sign or label to indicate the extinguisher’s location.